Designed to:
SICO Sewage Pump Controller is designed to monitor and maintain waste water level in wet well, monitor equipment status, annunciate all equipment malfunctions and alarms, provide all necessary system status, equipment malfunctions and alarms Data to BMS and/or SCADA Systems.
Consists of 3 Parts:
- Pumps
- Pump Control Panel
- Level Monitoring Instruments
Control Panel Features:
- Enclosure Type: NEMA 4
- Horsepower: 2-50 and beyond...
- Voltage: 208, 460 Vac
- Phase: 3
- Duplex and Triplex
- Combination Magnetic starters with thermal overload protection and external manual reset push buttons
- Auto & Manual alternator
- Second pump start delay
- High level alarm with audible and visual indication
- Low level alarm with audible and visual indication
- Overtempt. Alarm with audible and visual indication and shutdown for each pump
- Seal failure alarm with audible and visual Indication for each pump
- Hand-Off-Auto switch for each pump with drey contact for “OFF” position
- Horn with Silencer
- Push button
- Dry contacts for BMS
- Time Adjustable Pit Purge Procedure
- Submersible Liquid Level sensor
- (4-20 Ma) With Back-Up Floats
- (Redundant Level Control Circuit)
- SCADA Ready System
- MODBUS RS485 Communication for BMS
- HMI (Human Machine Interface) with Color Touch Screen
HMI:  Color touch screen: 7" Liquid crystal display panel Shows system status and alarms Provides access to set points, adjustments and commands
HMI is a bright color HMI touch screen with 320 X 240 pixels resolution. It has abilities of data acquisition, data processing, data logging, alarm management, alarm indication and communication.
HMI graphically presents the physical system components, their real time status with visual color change indication, alarm and operational set points.

|
|